PC9155 Wireless Alarm System
5-36
General Zone Fault & Restore
This reporting code is sent whenever a zone has entered the fault state. This occurs when there is a short on DEOL hardwired zones and/or a loss of supervisory on
a wireless zone. These reporting codes are sent to the System Maintenance call direction group.
Delinquency
The Delinquency Reporting code is transmitted in one of two ways. If section [380] option [8] is OFF, it is transmitted when the system has not been armed for the
number of days programmed in section [377]. If section [380] option [8] is ON, it is transmitted when no zone activity has been detected on the system for the num-
ber of hours programmed in section [377]. This reporting code is sent to the System Maintenance call direction group
.
General Zone Low Battery Alarm and Restore Codes
The following reporting codes are sent to report a Zone Low Battery condition on wireless zones. Individual zones are logged to the event buffer. SIA and Contact
I.D. formats identify the zone with the low battery condition. A zone low battery trouble is displayed immediately. Transmission may be delayed (section [377]).
These reporting codes are transmitted to the System Maintenance call direction group.
Installer Lead In and Lead Out
The Installer Lead In and Lead Out reporting codes are sent when the panel enters and exits Installer’s mode respectively. When exiting Installer Programming auto-
matically after initiating PC-Link via section [499], the Installer Lead Out event does not communicate until after the DLS session is complete. These reporting
codes are sent to the System Maintenance call direction group.
General System Supervisory and Restore
These reporting codes are transmitted via the System Maintenance call direction group when an enrolled TLXXX module has been detected as absent or restored.
[348] Test Transmission Reporting Codes
Walk Test Begin/End
These reporting codes are sent when the walk test is initiated and terminated. These codes precede and terminate the alarm reporting codes for the zones that are
activated during the walk test period, if the alarms are to be transmitted (section [382] option [2]). The walk test reporting codes are sent to the System Test Trans-
mission call direction group.
Periodic Test Transmission
When the programmed interval and time of day have elapsed, this reporting code is transmitted. This reporting code is sent to the System Test Transmission call
direction group.
System Test
When the [][6][Master Code][4] command is used to perform a manual system test, this reporting code is sent to test the communicator. This reporting code is
sent to the System Test Transmission call direction group.
[350] Communicator Format Options
This section requires four 2-digit entries (1 per phone number). See Appendix B: Communicator Format Options.
[351]-[376] Communicator Call Directions
Communicator call directions can be configured for 4 different phone numbers. Each reporting code falls under one of the following 5 groups:
• Alarms & Restores
• Openings & Closings
• Tampers & Restores (including System Tampers)
• System Maintenance Alarms & Restores
• System Test Transmissions
Each group can be assigned to the following call directions:
Option 1: 1
st
Telephone Number
Option 2: 2
nd
Telephone Number
Option 3: 3
rd
Telephone Number
Option 4: 4
th
Telephone Number
[377] Communication Variables
Swinger Shutdown (Alarms & Restores)
This value determines the number of transmission attempts (alarm and restore pairs) per zone that the communicator makes before it shuts down for that zone
(“Swinger Shutdown”). Program a 3-digit number from 000 to 014. When programmed as 000, the communicator Does NOT shutdown and all alarms are transmit-
ted. The bell and event buffer can follow Swinger Shutdown if they are enabled.
Swinger Shutdown (Tampers & Restores)
This value determines the number of times the same system Tamper type event occurs before stopping transmissions. Program a 3-digit number from 000 to 014.
When programmed as 000, the communicator does NOT shut down and all tampers are transmitted. This Swinger Shutdown affects zone and system tampers.
i
The Activity Delinquency timer is active when the system is armed in Stay mode, and not active in Away mode or Night mode arming.
i
If phone numbers are programmed for use with the TL265GS/GS2065 modules the programmed format must be SIA.